Wireless Addressable Optical Smoke Detector
SDW-1Info
Description:
The device is designed for early detection of fire outbreaks accompanied by the appearance of low-concentration smoke inside a controlled space in enclosed spaces of various buildings and structures, and transmission of "Fire" signal, as well as signals about its technical condition to the controllers of RUBETEK fire alarm system. It is used with CP-1 receiving and control device (Control Panel) and, through RE-1 radio expander, with SC-1 controller. Communication with system devices is carried out via RF 868 MHz wireless protocol
Available colors:
Main features:
- Early detection of fire
- Generation of "Fire" and "Fault" signals
- Automatic detection of the device in the system
- Detector testing using a laser tester or from the controller menu
- Performance monitoring
- Dust control
- Monitoring of the current smoke concentration value
- Battery status monitoring
- Tampering device against opening of the case
- Tampering device against separation from installation site
- Light indication of status
- Switching to service mode without interference with pairing and settings
- Protective cover
- Modern design
Specifications:
Connection type | RF 868 MHz |
Number of occupied address slots | 1 |
Power supply, V | Main: 3 V, CR123A 1500 mAh battery Backup: 3 V, CR2032 210 mAh battery |
Battery life | basic: at least 3 years standby: at least 3 months |
Sensitivity, dB/m | from 0.05 to 0.2 dB/m |
Maximum communication range (in open terrain), m | 900 |
Signal encryption | XTEA 128bit |
Number of channels within the frequency range, pcs | 5 |
Radiation power, MW, not more than | 25 |
Tamper alarm | yes |
Operating temperature, °C | from - 10 to + 55 |
Operating relative humidity, non-condensing | up to 93% at +40°C |
Case protection rating | IP20 |
Dimensions, mm | Ø 92 x 42 |
Weight, g, not more than | 105 |
Average service life, years | 10 |
Average time to failure, h | 60000 |
Downloads
TopDatasheets:
User manuals: