Rubetek Knowledge Base
Addressable manual call point

Addressable manual call point

MCP-1

Info

The device is designed for manual activation of "Fire" signal in RUBETEK addressable fire alarm system. It is used with CP-1 receiving and control device (Control Panel) and SC-1 controller. Equipped with a built-in short-circuit insulator.
  • Protection against accidental activation
  • Built-in short circuit isolator
  • Automatic detection of the device in the system
  • Performance monitoring
  • Tampering device against opening of the case
  • Light indication of status
  • Measurement of PLC voltage at the installation site
  • Switching to service mode without interference with pairing and settings
  • Modern design
Detector type A
Link interface PLC
Number of occupied address slots 1
Voltage supply via PLC
Current consumption, mA max 0,16 in standby mode
max 0,2 in «Fire» mode
Triggering at the force of pressing the button, N, not less than 25
Built-in isolator availalbe
Operation temperature range, °С from - 25 to + 55
Relative air humidity up to 93% at +40°С
Case protection degree IP20
Dimensions, mm 85 × 85 × 40
Weight, g, max 95
Tamper sensor available
Average lifetime, years 10
Average time between failures, h 60000