Rubetek Knowledge Base
Wireless Addressable Heat Detector

Wireless Addressable Heat Detector

HDW-1

Info

The device is designed to detect fire outbreaks accompanied by an increase in temperature inside the controlled space and transmit "Fire" signal, as well as signals about its technical condition to the controllers of RUBETEK fire alarm system. It is used with CP-1 receiving and control device (Control Panel) and, through RE-1 radio expander, with SC-1 controller. Communication with system devices is carried out via RF 868 MHz wireless protocol
Доступные цвета
Доступные цвета
  • Features two ways of determining fire outbreaks by the maximum temperature and by the rate of temperature rise
  • Generation of "Fire" and "Fault" signals
  • Automatic detection of the device in the system
  • Detector testing using a laser tester or from the controller menu
  • Performance monitoring
  • Battery status monitoring
  • Tampering device against opening of the case
  • Tampering device against separation from installation site
  • Light indication of status
  • Switching to service mode without interference with pairing and settings
  • Protective cover
  • Modern design
Connection type RF 868 MHz
Number of occupied address slots 1
Power supply, V Main: 3 V, CR123A 1500 mAh battery
Backup: 3 V, CR2032 210 mAh battery
Battery life Main: at least 3 years
Backup: at least 3 months
Maximum communication range (in open terrain), m 900
Signal encryption XTEA 128bit
Number of channels within the frequency range, pcs 5
Radiation power, MW, not more than 25
Tamper alarm yes
Operating temperature, °C from - 10 to + 55
Operating relative humidity, non-condensing up to 93% at +40°C
Detector class P
Class A1R rate of rise heat detection with fixed temperature up to 58°C
Class A1S fixed temperature heat detection up to 58°C
Class BS high fixed temperature heat detection up to 78°C
Dimensions, mm Ø 92 x 42
Case protection rating IP20
Weight, g, not more than 100
Average service life, years 10
Average time to failure, h 60000